DRC66NA
Main characteristics
- Compact dimensions
- Ecologic gas R134a
- Ermetic compressor
- Silent
- Three fan speed
- Functioning without water
- It can be ducted
- Rated average power consumption 840 W
- Air flow 560 mc/h
- Refrigerant R134a
- Weight 52 Kg
DRC66NA
DRC series dehumidifiers are used for humidity control and when the unit must be hidden inside the ceiling or for connecting the unit to an existing air conditioning system. The devices are particularly silent, the ducted versions are equipped with suction and discharge plenum and discharge plenum.
Characteristics
STRUCTURE
Dehumidifiers serious DRC consist of a body made of hot galvanized steel with removable panels for easy inspection and maintenance. The frame is pre-assembled, has brackets for fixing to the masonry.
COMPRESSOR
I the compressor is of type alternative hermetic , with the thermal protection device and acoustic insulation, is mounted on vibration dampers to reduce the vibrations.
REFRIGERANT CIRCUIT
Consisting of evaporator and condenser with copper pipes and aluminum fins 2.8 mm step. The cooling circuit is hermetically sealed. Capillary, filter drier in silica gel, high pressure (deu-climate version only).
FAN MOTOR
The fan inside the model DRC is centrifugal type impeller with d. 144 mm. Fan Motor with capacitor and switch to 6 speed.
AIR FILTER
Made of synthetic material made of polypropylene, the air filter is washable and easy to replace. It is mounted on wooden grid.
MICROPROCESSOR
Performs defrost control, the delay of the compressor and manages alarms through electronic control (deu-climate version).
PROTECTIVE EQUIPMENT
Low water pressure switch, breaking and fans (deu-climate version only).
CONDENSATE COLLECTION TRAY
INOX STEEL AISI 304
TESTING
Tests are carried out leaks in the circuit, testing and functional testing of electric shock.
TECHNICAL STANDARDS
This dehumidifier meets the essential requirements contained in the European Community Directive 2006/95/EC of 12 December 2006 on the safety of electrical products for use in low voltage, 2004/108/EC of 15 December 2004 relating to Electromagnetic Compatibility, 2006 / 42/CE of 17 May 2006 on the safety of machinery. Conformity is declared with reference to the following harmonized standards: CEI-EN 60335-2-40, IEC-EN 55014-1, CEI-EN 55014-2. It also states that the product is manufactured in compliance with RoHS Directive 2002/95/EC or in force, enforced by the Legislative Decree 151 July 25, 2005 (Article 5).
Technical data
Rated Average Power Consumption (at 25°C, 60% R.H.- water 16°C)
840 W
Max Power Consumption (at 32°C, 95% R.H.)
890 W
Absorbed Current (at 35°C, 95% R.H.) F.L.A.
5,2 A
Locked Rotor Current L.R.A.
30 A
Air Flow (with clean air filter)
560 mᶟ/h
Air flow range
550 ÷ 680 mc/h
Static nominal pressure
46 ÷ 22 Pa
Suond Pressure Level (at 3 mts in free field)
40 db(A)
Refrigerant
R134a
Condensed Draining Pipe Connection for rubber pipe diam.
16 mm
Functioning Temperature Range
10°- 33°C
Functioning Relative Humidity Range
45% - 95%
Width
858
Height
309
Depth
708
Weight (with case)
52 Kg