FD240TCR
Main characteristics
- Automatic dehumidostat
- High and low pressure switches
- Ecologic gas R410a
- Zinc plated and sturdy frame
- Powder painted
- Electronic management of defrosting
-
Rated average power consumption 3150 W
- Air flow 2300 mc/h
- Suond pressure level 56 db(A)
- Refrigerant R410a
- Weight 111+16 Kg
FD240TCR
The FD TCR series fixed dehumidifiers are high-performance appliances. This version is equipped with external condenser which enables dehumidification coupled with cooling, controlling humidity and temperature at the same time. They feature a washable air filter and must be connected to a fixed drain. They are equipped with an onboard mechanical dehumidostat. It should always be associated with a temperature control: digital thermostat. The dehumidifiers of the series TCR can be equipped with an optional HOT GAS defrosting system, with electronic and thermostatic control, and can work with temperatures close to 0 °C.
Characteristics
FRAME
Structure with panels made of sturdy galvanized steel, painted with epoxy powder ensuring high resistance to atmospheric agents and aggressive environments. The panels are removable to allow a quick inspection and maintenanceof the internal parts.
COMPRESSOR
Scroll compressor mounted on vibration dampers. Provided with resistance on the housing and thermal safety.
REFRIGERANT CIRCUIT
Evaporator and condenser: the coil is made of copper pipes and aluminium fins. Drying filter, Shrader valves, minimum and maximum pressure switch. Defrosting thermostat and solenoid valve in version S.
CONDENSATE COLLECTION TANK
The tank is in plastic non-corrosive, the dehumidifier should be connected to a fixed drain, preventing the formation of double siphons. Attach a tube with 3⁄4" F coupling to the welded fitting of the tank.
CONDENSATE LIFTING PUMP (OPTIONAL)
Pump on request.
IP
Standard IP21. On request IP44 (optional).
OUITSIDE UNIT
The remote condensers are made of copper pipes and aluminium fins. The diameter of the copper pipes is 3/8” and the thickness of the aluminium fins is 0,1 mm. The tubes are mechanically expanded into the aluminium fins to improve the heat exchange factor. The geometry of these condensers guarantees a low air side pressure drop and then the use of low rotation (and low noise emission) fans. The fans are axial type with aluminium aerofoil blades complete of the safety fan guard. The protection class of the motors is IP 54.
FAN
Centrifugal double suction fan, built with sturdy blades in galvanized sheet, statically and dynamically balanced. Protection degree: Three-speed fan.
HOT GAS DEFROST
Enables to use the dehumidifier in environments with temperature up to 3 °C. It is a special hot gas injection system to accelerate the defrosting of the ice formed in the evaporator.
AIR SUPPLY
The air supply is supplied as standard on the side opposite to the air inlet, but you may require the dehumidifier in TOP version (with delivery on the top side of the machine).
AIR FILTER
The air filter, supplied as standard with the unit, is washable and easily replaceable. It is in Polyurethane and High-efficiency filter.
MICROPROCESSOR
Controls the defrosting cycles, the compressor timer and the alarm card. The dehumidifier is equipped with step sequence control and electronic control 0-10 V (optional) or on/off of the outside unit.
CONTROL PANEL AND ELECTRICAL CONTROL PANEL
Located in the side area of the machine. IP protection degree. Made in compliance with the European standards 73/23 and 89/336.
TESTING
Tests are performed to check the tightness of the refrigeration circuit. Electrical discharge tests and functional tests are performed as well.
Technical data
Average rated power consumption (20 ºC - 60% R.H.)
3,7 kW
Maximum power consumption (35 ºC - 95% R.H.)
4,3 kW
Maximum current consumption (35 ºC - 95% R.H.) F.L.A.
9,1 A
Start up current L.R.A.
50 A
Sound pressure level (3 meters in open field)
55 db (A)
Refrigerant
R410a
Fitting on the machine for condensate drain
¾”
Operational range (temperatures)
7÷35 °C
Operational range (temperatures) with optional hot gas defrosting system
0,5÷35 °C
Operational range (temperatures) with optional under 0°c defrost system
-0,5÷35 °C
Operating range (relative humidity) T < 30 °C
45÷99%
Operating range (relative humidity) T 30÷32 °C
45-80%
Operating range (relative humidity) T 32÷35 °C
45-70%
Average rated power consumption (20 ºC - 60% R.H.) with 4kW resistors
7,7 kW
Hot water coil heating capacity (environment 27°C, water 60/70 °C)
5 kW
Avaiable voltage
400/3N~/50
Width
976
Height
580
Depth
682
Weight
110+16